Supply Voltage : 12 to 30 Vdc
Operating Current : 10mA (normal operation) 27mA (alarm relay activated)
Alarm Output : Non-latching alarm normally open volt free contacts Contact rating 1A @ 30Vdc (resistive load), 0.3A @ 110Vdc (resistive load)
Fault Output : Normally closed onto isolated output (opening on power loss or open circuit of detection cable) 20mA @ 48Vdc (resistive load) Important Note - the fault output is not current limited. Exceeding the specified current limit on the fault output will damage the fault output circuit beyond repair
Operating Temperature : 0 to 50ºC (32 to 120ºF)
Cable Length per Control Module : 3.75m (12ft) to 1000m (3280Ft)
Sensitivity : A minimum amount of water must be in contact in a continuous length along the detection cable to trigger an alarm. For example a pool of water 5mm (0.2") deep x 50mm (2") wide x 200mm (8") long. Water must submerge the cable to a depth sufficient enough to come in contact with both black cores for an alarm to be triggered.
Reset : The control module will automatically reset when the cable is dry
Data Cable Connections : 1m x 6 core data cable, core Size 22AWG (Ø0.65mm) Overall Diameter 5.3mm (0.208”) Power, alarm volt free contact and fault monitoring