Detection zones : 2 zone or 4 zones of water detection cable.
End of Line device : 4k7 Ohm 5% 0.25w resistor
IP rating : IP30
Operating temperature : (°c) -5°c to +40°c
Operating humidity <95%
Standby current : 75mA (2 zone) 85mA (4 zone)
Alarm circuits : 2 fully monitored, each fused @500mA
Alarm load : 800ma shared between all sounder outputs.
Common alarm relay : Volt free no/c/nc contact rated 3 amp @30 Vdc
Common fault relay : Volt free no/c/nc contact rated 3 amp @30 Vdc
External inputs : Class change and Alert pulse sounders Non latching switched –ve inputs. Max input voltage 28Vdc
Outputs : Water alarm and fault common outputs Switched –ve voltage outputs for external relay control, max load 40mA
Mains supply & fuse : 230vac +10 / -15% 50Hz protected by 2 Amp fuse
Battery charging voltage : 27.3 Vdc @20OC
Auxiliary supply to field accessories : 28Vdc fused @ 500mA
Max. battery size & space : 2 x 3.2Ahr 12volt VRLA ( Use Yuasa NP range batteries)
Terminal capacity : 0.5mm2 to 2.5mm2
Cable entry : 13 x 20mm top entry knockouts 7 x 20mm rear entry knockouts
Enclosure material and colour : Mild Steel, Epoxy powder coated silver grey Colour ref: Radon MW334E Interpon powder coat
Panel dimensions : (mm W x H x D) 308 x 260 x 80